Fan Power Characterization
Setup
NF-F12 industrialPPC-3000 PWM Datasheet
Wire Pinout:
Setup: The fan was held in an upright position connected to the Keysight DC power supply.
For air speed: Using battery-box set-up (cardboard box enclosure) with an anemometer connected to the end
Single Fan
Voltage (V) | Current (A) | Power (W) | Air Speed (m/s) |
---|---|---|---|
6 | 0.085 | 0.510 | 2.4 |
7 | 0.111 | 0.777 | 2.7 |
8 | 0.137 | 1.096 | 3.0 |
9 | 0.165 | 1.485 | 3.4 |
10 | 0.185 | 1.850 | 3.6 |
11 | 0.215 | 2.365 | 3.9 |
12 | 0.242 | 2.904 | 4.2 |
13 | 0.273 | 3.549 | 4.5 |
14 | 0.307 | 4.298 | 4.8 |
15 | 0.340 | 5.100 | 5.0 |
Two Fans in Parallel
Voltage (V) | Current (A) | Power (W) |
---|---|---|
6 | 0.170 | 1.020 |
7 | 0.215 | 1.505 |
8 | 0.264 | 2.112 |
9 | 0.313 | 2.817 |
10 | 0.368 | 3.680 |
11 | 0.423 | 4.653 |
12 | 0.480 | 5.760 |
13 | 0.540 | 7.020 |
14 | 0.610 | 8.540 |
15 | 0.678 | 10.170 |
Two Fans in Series
at 13V the fans blow very inconsistently for 60s until coming to a complete stop
Powering at 14V seems to provide inconsistent results
only starts-up 50% of the time (either taking some time to start or does not start at all)
takes around anytime from 10s to 30s to start-up
Startup times for 15V is also inconsistent starting-up
can take anywhere from 8s to 45s for the fans to properly blow
Voltage (V) | Current (A) | Power (W) |
---|---|---|
14 | 0.107 | 1.498 |
15 | 0.122 | 1.830 |
16 | 0.132 | 2.112 |
17 | 0.145 | 2.465 |
18 | 0.158 | 2.844 |
19 | 0.172 | 3.268 |
20 | 0.185 | 3.700 |