Fuses selection for MSXIV

Power calculation


nom Powermax Powernom current dischargemax current dischargenom current charge (drive)max current charge (drive)nom current charge (Idel)max current charge (idel)
Battery

000000
Charger Interface
33000
00-21.82539683-21.82539683
Motor 12000500015.2835090940.21976077-15.28350909-40.2197607700
Motor 22000500015.2835090940.21976077-15.28350909-40.2197607700
Solar-592.5-118500-4.527739569-9.055479138-4.527739569-9.055479138
Pre-charger


2.10000
DC DC362780.2751031642.1244077640000
motor controller
18446.4





motor controller
18446.4
















Total current30.8421213584.66392931-35.09475776-89.49500068-26.35313639-30.88087596

Fuse calculation

IEC ampacity (A/m2)1.3cyclic load1.3alt(min)2500alt(max)2600Kx0.8








currentKt(min) (T=60C)Kt(max) (T=60C)Kt(max) (T=45C)Wire diameterCross sectional area100% cable area% cable usedKeKvKa(min)Ka(max)I(rating) maxI rating minwire current ratingmaxium fuse
Battery fuse84.663929310.8450.9
6.1529.7057220465.126099470.4561262270.9510.9750.97165.0368992144.8198791255191.25EXRAD-XLX-4X
Charger fuse21.825396830.90.90.952.588265.26145284716.788766790.3133912640.9110.9750.9742.0771097538.97392297354.75Awg 8
Motor fuse 140.219760770.8450.9
4.9519.244218530.938277520.6220197130.9510.9750.9778.4010931268.79695922155116.25EXRAD-XLX-6X
Motor fuse 240.219760770.8450.9
4.9519.244218530.938277520.6220197130.9510.9750.9778.4010931268.79695922155116.25EXRAD-XLX-6X
Solar fuse9.0554791380.8450.9
1.628142.0819647576.9657531830.2988858060.910.9750.9718.6326731216.350170673224Awg 14
Pre-charger fuse2.10.8450.9
1.023620.822938551.6153846150.509438150.9510.9750.974.0935672513.5921052631612Awg 18
DC DC fuse2.1244077640.8450.9
1.023620.822938551.6341598180.5035851090.9510.9750.974.1411457393.6338553861612Awg 18

Thermal derating (Kt)

Thermal connection derating (Ke)

Recomendation


Fusecurrent rating
battery fuseXEV25-175175
Charger fuseXEV10-5050
Motor fuse 1XEV20-8080
Motor fuse 2XEV20-8080
Solar fuseXEV10-2020
Pre-charger fuseXEV10-55
DC DC fuseXEV10-55

For the lower-current fuses (Solar, Pre-charger, DC-DC), we will be using the axial bolt-on type.


Power calculation excel doc 

Fuse calculation excel doc


Alternate Sources for fuses (since COVID happened and Eaton was not going to sponsor for a while)



Note On Interrupting Rating:

Fuses on our HV system should be able to project against a short circuit condition on the cables they are connected to. So what's the short circuit current?

The max current available from our batteries will be at their highest voltage, since a short circuit is just a resistive load. Maximum condition calculations will assume that the external short is 0mOhm, and the only thing limiting the current is the battery's internal resistance. This is a reasonable estimation as it will ensure an adequate safety factor for our fuses. Since our modules are in series, we only need to do the calculation for 1 module.

Voltage: 4.2V

Internal Impedance (using AC since a short circuit is a transient event, and AC IR is lower than DC IR typically): 25mOhm (ish - rough value of what was observed)

Short circuit current per cell (Iscc) = 4.2/0.025 = 168A

Short circuit current per module = 168A * 25 cells = 4200A = 4.2kA.


So all of our fuses must be rated to break a minimum of around 4.2kA.