Alternate Sources for fuses (since COVID happened and Eaton was not going to sponsor for a while)
View file | ||||
---|---|---|---|---|
|
Note On Interrupting Rating:
Fuses on our HV system should be able to project against a short circuit condition on the cables they are connected to. So what's the short circuit current?
The max current available from our batteries will be at their highest voltage, since a short circuit is just a resistive load. Maximum condition calculations will assume that the external short is 0mOhm, and the only thing limiting the current is the battery's internal resistance. This is a reasonable estimation as it will ensure an adequate safety factor for our fuses. Since our modules are in series, we only need to do the calculation for 1 module.
Voltage: 4.2V
Internal Impedance (using AC since a short circuit is a transient event, and AC IR is lower than DC IR typically): 25mOhm (ish - rough value of what was observed)
Short circuit current per cell (Iscc) = 4.2/0.025 = 168A
Short circuit current per module = 168A * 25 cells = 4200A = 4.2kA.
So all of our fuses must be rated to break a minimum of around 4.2kA.