Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

The following table should outline results from varying the E-load and intensity of the sunlight. The first cell in series was isolated, and attached to an E-load.

Light SourceV(in)ocE-Load SettingMeasured Voltage OutputMeasured Current extra notes
Sunlight25.131



Clouds16.27.0kohm10.030.0014
Clouds16.210ohm0.1550.0152
Clouds16.270Wbasically 00.015
240W light9V5ohm0.2270.0422reading the vout from mppt was 0.56V while output from solarsenseslave was 0.056V
240W light.866 (dmm) 25V(eload off)5ohm.2850.0566






Note: when the Mppts are lit by the light outside on a fully cloudy day, the mppt goes into short circuit mode where it provides basically no output voltage increase for a normal resistance on the line. However, using the 240W flashlights provided by Micah, we are able to see a huge increase in the voltage input and the voltage out on the line (from 15V(out)oc when cloudy to 25V(out)oc). On a sunny day outside the voltage output from the mppt is still 25V which is pretty good.

...

Due to the variance in the measuremntes, each mppt was taken out of the holders and tested with the bench supply and DC E-Load. The following table summarizes the results. Note that the input open circuit voltage was set to 27V by the output voltage setting potentiometer. The input open circuit voltage (voltage from power supply) should also always start at 20V (unless modified in the notes).

MPPT#DC E-Load SettingsV(in)ocV(out)ocVinVoutIinIoutmax temp (deg C)Notes
16ohm15.9825.24510.0118.5166.2643.0874424-25V has audible frequency oscillations (can hear)
17ohm15.9825.24533.0132.3394.6084.6231.3When in audible range, heat increases really quickly. With an increase in resistance on the E-load is a increase in the voltage output with a significant decrease in the output current for a total less amount of output power (of course its following the inverse exponential curve until open circuit voltage in this case → infinite impedance). 
16ohm---25.6225.7684.2749during the time of this testing I also wanted to test the efficiency loss from running the mppt with an input voltage of 25-27V, in which the DCDC operates at an  audible frequency of oscillations. Before the testing, I noticed that there was an increase in temperature at this frequency, so I wanted to find out the loss in efficiency. It was concluded that the loss in about 6 watts at this point, which was about the same power loss as at 20V input. It seems that the audible noise comes from the fact that the input voltage matches the upper limit of the output voltage determined by the output potentiometer.
26ohm---25.7215.874.28950preformed similarily to mppt #1 except that running it at 27V was 1W less efficient than under 27V.
35ohm---25.6066.9385.120643The power drop for this testing (as outlined) was 7W (about 1W more than normal)
46ohm---25.5495.7434.25649About a 6.5W drop in efficiency.
56ohm---25.6965.7934.28355Preforms similarly to the others, except gets to a higher temperature even though just 6W drop
66ohm---25.7065.8164.28455Preforms similarly to the others, (6W drop)


V(in)oc & V(out)oc were measured without an electronic load connected.

...

The following table outlines the results:

Current input MPPT1Current Input MPPT2DC Load VoltageDC Load CurrentDC Load ResistanceMax TemperatureNotes
0.9060.98550.5430.721870negligibleWhen the resistance is decreased so that one of the mppts goes into constant current mode, the mppt cannot stabilize itself at a specific voltage, and instead fluctuates like crazy. This may be an issue if a mppt needs to maintain a certain current output, and one mppt lags behind others. Also in any case, one (or both) of the mppts will have fluctuating current (before current limit is met) in order to keep a constant current from the constant resistance.
2.8192.59549.9072.07872432.5was using two power supplies limited to 3A output (still decreased CR value until one of them went into constant current mode) 20V input for this and above on power supplies
2.8182.60557.7592.5952030Input on mppt 1 is 25V and on 2 is 32V (limits of the power supplies)





























Array testing

This test will determine the power out of the arrays at 12pm on a cloudy day (to be repeated on a sunny day) the test will simply put each section of the array in constant resistance mode, and measure the output voltage and current (essentially the power). The eload will be set to 1kohm in constant resistance mode then again at 10ohms.


MPPT #Resistance (Load)VoltageCurrent
1100015.9180.01533
1100.6710.0667
2100015.9370.1553
2100.7310.073
3100016.3320.0161
3100.7450.0742
4100016.4370.0161
4100.8660.0863
5100016.5910.0159
5100.8330.0831
6100016.5630.0159
6100.9310.0929


To conclude this testing, the only way that the cells are the point of failure is if in direct sunlight they still do not have a sufficient power output. I will try to test this, however it is winter so getting the car outside may be a little tricky.

...

SPI Communication Testing of MPPTs

...