We observe for each thickness the ampacity is best modelled using a power equation. We generate the following table of extrapolated points using the more conservative 1/8" model. We expect this to bound bus bars of smaller thickness (such as 1/32"). All areas are rounded up to the nearest tenth. Note that in the 60 A - 90 A region the area relationship is approximately linear, but this does not hold true for the entire dataset.
Ampacity (A) | Projected Area (sq. mm) |
---|---|
90 | 22.3 |
80 | 19.5 |
70 | 16.7 |
60 | 13.9 |
Recommendations
We recommend a hard lower bound on bus bar area of 17 sq. mm, corresponding to an ampacity of at around 70 A with a 30°C rise. This should give a moderate safety factor to ensure a temperature rise lower than 30°C at a 50 A load. Where practical from an engineering tradeoff standpoint, larger areas should be selected to provide further confidence and design margin during peak operating conditions.